Using Gauges for Troubleshooting
Air in cooling system (insufficient suction)
Defective expansion valve
Excessive refrigerant
Insufficient compressor operation
Insufficient refrigerant
Moisture Intrusion
Refrigerant does not circulate

Summary Table of Gauge Diagnostics





Pressure Range
Low side: 36 to 50 psi
High side: 284 to 356 psi
Indications
Both pressures are TOO HIGH
The low-side piping is not cold
Causes
Air in the system
Remedy
Evacuate the system
Replenish the refrigerant
Check the gauge readings
If prolonged operation with air in the system, the liquid tank must be replaced.





Request Information
ISO 9001:2008 News

Please put in your name


Enter a valid email addressInvalid format.


Enter your phone number Invalid format.

Yes! send me industry updates

Question or Request?


Perrin Manufacturing is committed to providing you with superior products and services; we renew this pledge through continual improvement of our products and motivation of our staff.

We faithfully comply with all of the requirements of our ISO 9001:2008 Quality Management System, the most current edition of the standard. Beyond that, our highly trained quality staff persistently search for new ways to improve the effectiveness of our system.
iso 9001 management quality iso 9001 management quality iso 9001 management quality